JZ-0.6BF On-load Tap Changer Online Oil Filtering Machine
I.Product Features:
-
JZ Series Oil Purifier for On Load Switch/Tap-Changer is mainly used for cyclic purification of the oil from bypass of the
transformer and high voltage switch.
-
It can effectively absorb the slight water and prevent the small mechanical particles by cyclic
purifying system of the bypass while the main system is under normal working.
-
control the oil cleanness and dielectric strength in order to ensure the electrical parameter such as water content,flash point,break-down voltage and cleanness of the
insulation oil, will not lower, and extend the repairing period and the life span of the transformer and high voltage switch.it ensures that the high volatge switch works safely during
maintenance period.
-
Integrate the function of fineness filtration and dehydration.
-
it can effciently remove dissolved water, and control the water content,flash point and dielectrical strength.
-
it can efficiently remove particles in the oil, so that control the oil cleanness up to
Nas6
-
High filtration efficiency,simple to opera te, no-man supervision.
-
All the pipes use stainless steel,no secondary pollution happens during the filtration process.
-
Particles filtration systerm, large filtration areas and high filtration efficiency,equiped with filtation protection device to realise automatic alrming when the overpressure
happens.
-
Advanced filter adsorption technology,without heater.The adsorption filter is madeby special material, with low energy consumption.
-
Less driving components,only oil pump is used in filtration process,low energy consumption, reliable.
-
Use special-purposed oil pump, no leakage, low running noise and long use-span.
-
The whole machine is controlled automatically.
II.Same Series Products:
Item
|
Name of parameter
|
Type Unit
|
JZ-0.6BF
|
Technical parameter of the equipment
|
Nominal flow capacity
|
L/Hour
|
600
|
Working pressure
|
Mpa
|
≤0.5
|
Working temperature og oil
|
°C
|
20~40
|
Working power
|
|
3-Phase 4-wire(380V-50HZ)
|
Total electric power
|
KW
|
0.3
|
Diameter of inlet-outlet hose
|
DN
|
15/15
|
Out Size
|
Length
|
cm
|
75
|
Width
|
cm
|
36
|
Height
|
cm
|
110
|
Weight
|
Kg
|
50
|
Oil Treatment Index
|
Filtering accuracy
|
um
|
1
|
Cleanness
|
NAS Grade
|
≤6
|