VLF Series Very Low Frequency Generator Insulation Test set

  • Place of Origin:Chongqing of China


1 Application

Very Low Frequency Generator Insulation Test set is applied in power cable and generator insulation test in power system.



2 Technical Index

1 Max voltage output: refer to table 1

2 Output frequency: 0.1Hz, 0.05Hz, 0.02Hz

3 Measurement error < 3%RDG+0.3%FS

4 Positive and negative voltage peak errors < 3%RDG+0.3%FS

5 Power supply:AC220V ± 10%, 50Hz/60Hz

6 Voltage wave form distortion: <5%

7 Environment temperature: 050C

8 Humidity: ≤85RH



3 Parameters for very low frequency tester

Model no Rated Voltage/current Load Carrying Capacity Power Fuse Tube
VLF-30 30kV/20mA

(Peak)

0.1Hz,≤1.1µF 8A
0.05Hz,2.2µF
0.02Hz,5.5µF
VLF-50 50kV/30mA

(Peak)

0.1Hz,≤1.1µF 10A
0.05Hz,≤2.2µF
0.02Hz,≤5.5µF
VLF-60 60kV/50mA

(Peak)

0.1Hz,≤0.5µF 10A
0.05Hz,≤1µF
0.02Hz,≤2.5µF
VLF-80 80kV/30mA

(Peak)

0.1Hz,≤0.5µF 12A
0.05Hz,≤1µF
0.02Hz,≤2.5µF

重庆格纳迪机电设备有限公司

重庆市南岸区南坪金台大厦9-10 Tel: 86-023-62984892 Fax: 86-023-62940030 Mobile: 15123029636 Country: China (Mainland)